Waste Incinerators Specification
To provide for diesel service tank (Capacity 400 litres) including level indicator
The tank should be connected to the incinerator at a higher level to enable free-flow of diesel from the tank to the incinerator. The 
connecting pipe must be a black pipe of approved gauge and diameter. Include other accompanying accessories and fittings
Installation & commissioning works
Positioning of Incinerator: –
 Provide lifting gears as forklift, gantry, rollers, and lifting jacks and position incinerator.
Connect burners to fuel supply.
Chimney Installation:
Composition of the chimney: –
Provide a chimney with scrubber (for filtration)
Provide lifting gear to hoist, erect and mount chimney, and provide supports slings as necessary. Allow for cutting of tree branches to 
facilitate the exercise.
The chimney shall be painted with approved heat resistant paint after installation.
Feed Capacity 600-1200 kg per feed 600-1200 kg per feed
Burning Rate Min. 300 kgs per hour Min. 300 kgs per hour
Burning Time per Feed 2-4 hours 2-4 hours
Voltage 380V 220V/380V
Power 1.48Kw 1.48Kw
Frequency 50Hz 50Hz
Fuel Natural Gas or Diesel Oil Natural Gas or Diesel Oil
Fuel Mode Manual Manual
Fuel Consumption (Oil) Max 40 kgs per hour 31.0-59.0 kgs/houruel Consumption (Gas) Max 44 m3 per hour
Waste Combustion Chamber 2400 liters 2400 liters
Post Combustion Chamber 1200 liters 1200 liters
Oil Tank Capacity 500 liters 500 liters
Chimney 10.0 M 10.0 M
Chamber Material Firebrick, Refractory Concrete Firebrick, Refractory Concrete
Max. Heat Value 340,000 Kcal per hour 590,000 Kcal per hour

Operation Technical Specification
Solid Chamber Temperature 800 Deg. C – 1000 deg. C 800 Deg. C – 1000 deg. C
Gas Chamber Temperature 1000 Deg. C – 1200 deg. C 1000 Deg. C – 1200 deg. C
Chamber Anti-Rate 1450 Deg. C 1450 Deg. C
Residency Time 2.0 Sec. 2.0 Sec.
Burning efficiency >98% >98%
Waste Lower Calorific Power 3000 Kcal 3000 Kcal